Item | Unit | VACFR12-12D/T125-31.5 | |
Rated voltage | kV | 12 | |
Rated frequency | Hz | 50 | |
Rated current | A | 125 | |
1 min power frequency withstand voltage | kV | Phase to phase,to earth 42;isolating fracture 48 | |
Lightning impulse withstand voltage | kV | Phase to phase,to earth 75;isolating fracture 85 | |
Rated thermal stability current | kA | 20(4s) | |
Rated dynamic stability current | kA | 50 | |
Rated making current(peak) | kA | 50 | |
Rated short circuit breaking current(expected value) | kA | 31.5 | |
Critical breaking current max.1(2).T | kA | As per fuse characteristic curve | |
Min.breaking current | kA | As per fuse characteristic curve | |
Rated shift current | kA | 1.2 | |
Max,breaking current | kA | 1.8 | |
Breaking no-load transformer capacity | kVA | 1250 | |
Rated cable charged current | A | 10 | |
Breaking times of rated power load current | times | 6000 | |
Opening time of striker with load switch | s | <0.06 | |
Thermal stability current of earth switch | kA | 20(2s) | |
Dynamic stability current of earth switch(peak) | kA | 50 | |
Power voltage of motor operation | V | AC/DC 220 |
Item | Unit | Data | |
VACFR12-12D/T125-31.5 | |||
Moving contact travel | mm | 200(+8,-2) | |
Inter-phase center distance(before mechanism stored energy) | mm | 210±1.5 | |
Moving contact opening distance | mm | 40±2 | |
Opening clearance between auxiliary contact | mm | ≥150 | |
Tri-phase closing/opening asynchronous | ms | ≤3 | |
Just off speed | m/s | ≥2.8 | |
Just on speed | m/s | ≥3.8 | |
Distance between metal value to conduct tube | mm | ≥125 | |
Fracture distance of earth switch | mm | ≥150 | |
Main loop resistance | μΩ | ≤300 | |
Max operating torque | N.m | ≤160 |