Customization: | Available |
---|---|
Certification: | CCC, ISO9001, GB |
Shell Material: | Stainless Steel |
Still deciding? Get samples of US$ 1000/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW7-40.5kV Series Outdoor H.V. VCB - the ultimate electrical appliance equipment for all your power needs! With its tri-phase AC 50Hz and rated voltage of 40.5kV, this high-voltage circuit breaker is a force to be reckoned with. Equipped with both spring operation mechanism and electromagnetism operation mechanism, it offers the convenience of far control electrically operated opening and closing, as well as the option for manual energy storage and manual opening and closing. Talk about versatility!
But that's not all - the design performance of the ZW7-40.5kV VCB meets the requirements of both the national standard GB1984 AC H.V. Circuit Breaker and the IEC standard IEC-65 High Voltage AC Circuit Breaker. So you can rest assured that you're getting a top-notch product that adheres to the highest industry standards.
Now, let's talk about its applications. The ZW7-40.5kV vacuum circuit breaker is specifically designed for outdoor use in 40.5kV power transformer systems. It's perfect for control and protection purposes, making it an ideal choice for normal operation and short circuit protection in city and township power distribution networks, as well as in various industries and mining enterprises. This circuit breaker is truly a game-changer!
When it comes to structure, the ZW7-40.5kV VCB boasts a porcelain insulator column type design. The upper porcelain insulator houses the vacuum interrupter, while the lower porcelain insulator serves as the prop porce. This thoughtful design ensures optimal performance and durability.
Item | Unit | Data | |||
Rated voltage | kV | 40.5 | |||
Rated current | A | 1600 | 2000 | ||
Rated short circuit breaking current | kA | 25 | 31.5 | ||
Rated short circuit making current (peak) | kA | 63 | 80 | ||
Rated short time withstand (thermal stable) current | kA | 25 | 31.5 | ||
Rated peak value withstand(dynamic) current | kA | 63 | 80 | ||
Rated short-circuit duration | S | 4 | |||
Rated insulation level | Lightning impulse withstand voltage (peak) | kV | 185 | ||
Rated insulation level | 1min power frequency withstand voltage | Dry type | kV | 95 | |
Rated insulation level | Wet type | kV | 80 | ||
Rated operation sequences | O-0.3s-CO-180s-CO | ||||
Breaking times of rated short-circuit breaking current | time | 20 | |||
Full breaking time(to match spring operating device) | ms | ≤80 | |||
Mechanical life | time | 6000 | |||
Rated operating voltage | V | 220 | |||
Opening distance of contact | mm | 22±2 | |||
Over travel of contact | mm | 5±1 | |||
Bounce time | ms | ≤5 | |||
Each phase circuit DC resistance | μΩ | ≤120 | |||
Outline dimension(length×height×width) | mm | 2335×2275×500 | |||
Whole weight of circuit breaker and mechanism | kg | 1100 |