Get ready to experience the power of VACYC permanent magnet AC M.V. vacuum contactor and VACFC series AC M.V. vacuum contactor-fuse combination apparatus (F-C)! These three-phase AC indoor middle voltage switch devices are perfect for AC 50-60Hz and have a rated working voltage of 7.2kV and 12kV. With their flexible function combination, compact and reliable structure, multiple protection functions, long service life, and frequent operation capabilities, these devices are the ultimate solution for opening and closing load circuits such as AC motors and transformers. Plus, they can also be used for capacitor reactive power compensation.
The VACFC series combination apparatus features a modular combination structure that can be used by a single contactor or combined into F-C. It can be fixed or drawout moving type, and the drawout type can be used with KYN28A(GZS1) intermediate cabinet with a width of 650mm or 800mm. It's the perfect replacement for VSC/P contactor.a. Environment temperature: -5ºC~+40ºC, and the average value is no more than +35ºC within 24 hours.
b. Altitude: no more than 1000m.
c. Atmospheric conditions: monthly highest humidity in the wettest month is no more than 90% and the monthly average minimum temperature shall be 25ºC. Condensation on the products due to temperature changes shall be considered.
d. Impact vibration: The place is without extensive shaking, impact, and vibration.
e. The place is without explosion hazards, enchant gas, and sleet.
f. No rain and snow in places
g. Pollution degree: Three grade
h. Installation type: III
i. Installation condition: The slant angle between the installation surface and the vertical surface is no more than 15°.
Item | Unit | VACYC | VACFC | ||
Rated voltage | kV | 12 | 7.2 | 12 | 7.2 |
Rated current | A | 400 | 25-160 | 25-315 | |
Rated breaking current | kA | 3.2 | 40 | ||
Rated making current | kA | 4 | - | ||
Limit breaking capacity | kA | 4.5 | 40(100peak value) | ||
4s rated short time withstand current | kA | 4 | - | ||
Peak withstand current | kA | 10 | - | ||
1s overload withstand current | kA | 6 | - | ||
Rated transfer current | kA | - | 3.15 | ||
1 min rated power frequency withstand voltage | kV | 42 | 32 | 42 | 32 |
Lightning impulse withstand voltage | kV | 75 | 60 | 75 | 60 |
Power frequency withstand voltage of control circuit | kV | 2 | 2 | ||
Rated operating voltage | V | 220V(AC/DC optional) | |||
Operating voltage range | V | 75%-100% Ue | |||
Maximum operating current | A | <7.5 | |||
Rated current of auxiliary contact | A | 5 | |||
Life electrical AC3 | Thousand times | 25 | |||
Life electrical AC4 | Thousand times | 10 | |||
Life mechanical | Thousand times | 50 | |||
Rated operating frequency | times/h | 300 | |||
Short time operating frequency | 20s | 600 | |||
Closing time | ms | ≤40 | |||
Opening time | ms | ≤35 | |||
Average closing speed | m/s | ≥0.4 | |||
Average opening speed | m/s | ≥0.45 | |||
Three phase non-simultaneity | ms | ≤5 | |||
Clearance between open contacts | ms | ≥5 | ≥3.5 | ≥5 | ≥3.5 |
Over travel | mm | ≥1.5 | |||
Main circuit resistance | μΩ | ≤150 | ≤150 Not including fuse |