Customization: | Available |
---|---|
Certification: | CCC, ISO9001, GB |
Shell Material: | Stainless Steel |
Still deciding? Get samples of US$ 1000/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the 12kv Outdoor High Voltage Vacuum Circuit Breaker on Pole, the ultimate solution for all your circuit breaking needs! This cutting-edge product is designed to provide exceptional performance and reliability in outdoor environments, making it the perfect choice for various industrial applications.
With its advanced technology and innovative design, this Vacuum Circuit Breaker (VCB) on Pole offers unparalleled efficiency and safety. It is specifically engineered to handle high voltage operations, ensuring smooth and reliable circuit breaking in the most demanding conditions. Whether you need to break or close load current, overload current, or short circuit current, this circuit breaker has got you covered.
The ZW20A-12C type AC H.V. vacuum pole automatic controller is specifically designed for use in tri-phase electric systems with an AC frequency of 50Hz and a rated voltage of 12kV. This means that it is perfectly suited for a wide range of applications, including power distribution, industrial plants, and infrastructure projects.
Safety is always a top priority, and this circuit breaker excels in this aspect. It incorporates advanced safety features, such as arc extinguishing technology and fault protection mechanisms, to ensure the protection of both personnel and equipment. This guarantees a secure and efficient operation, minimizing the risk of accidents and downtime.
In conclusion, the 12kv Outdoor High Voltage Vacuum Circuit Breaker on Pole is a game-changer in the world of circuit breaking. Its exceptional performance, reliability, and safety features make it the ideal choice for any B2B platform. So, why settle for anything less when you can have the best? Upgrade to this outstanding VCB on Pole and experience the excitement and spirit of cutting-edge technology!
The controller is an intelligent device, that matches sectionalized to reach distribution automation without other control system. Consist of a circuit breaker (with mechanism operation), controller, and control power, besides opening of closing regular and fault current as the circuit breaker, it can repeatedly auto reclosing by advanced setting times for sectionalized to isolate fault circuits when the short circuit fault happens. The non-fault lines will resume the power supply; if repeatedly auto reclosing failed, closing and interlock inside of the controller, another side of the network, originally closing and interlock status will remove interlock and auto closing, non-fault lines resume power supply at once. The network automation could limit the power supply interrupted district to a minimum range, it has high social benefit and economic benefits.
The product is practical and reliable, multiple functional, the controller uses a microprocessor, the panel shown in digital, conveniently with person-machine talking, all the parameters could be adjusted, a new function of the GPRS communication system could achieve opening, and closing operation and Teradata communication function by mobile phone, it can transmit lines parameters and running state of the equipment.
Item | Unit | Date |
Rated voltage | kV | 12 |
Rated frequency | Hz | 50 |
Rated current | A | 630,1000 |
Rated short circuit breaking current | kA | 16,20,25 |
Rated peak value withstand current | kA | 40,50,63 |
Rated short time withstand current (4s) | kA | 16,20,25 |
Rated short circuit making current (peak) | kA | 40,50,63 |
Mechanical life | time | 10000 |
Rated current breaking times | time | 10000 |
Breaking times of rated short circuit current | time | 30 |
P.F. withstand voltage (1 min): inter-phase; to earth, fracture | kV | 42/48 |
Lightning impulse withstand voltage; inter-phase; to earth, fracture | kV | 75/85 |
Secondary circuit 1 min power frequency withstand voltage | kV | 2 |
Net weight | kg | 140 |
Item | Unit | Data |
Opening distance between contacts | mm | 9+1(-0.5) |
Contact over travel | mm | 3+1(-0.5) |
Opening speed | m/s | 1.2±0.2 |
Closing speed | m/s | 0.6±0.2 |
Contact closing bounce time | ms | ≤2 |
Central distance between phases | mm | 135±1.5 |
Insulation distance of outer electrified air | mm | 240±2 |
Outer creepage | cm/kV | 3.8 |
Tri-phase opening asynchronous | ms | ≤2 |
Each-phase conductive circuit resistance | µΩ | ≤150 |
Closing time | ms | ≤45 |
Opening time | ms | ≤45 |
Rated power of energy-stored motor | W | ≯40 |
Rated voltage of energy-stored motor | V | AC220 |
Rated closing operation voltage | V | AC220 |
Max./min. closing operation voltage | V | AC264/143 |
Rated opening operation voltage | V | AC220 |
Max./min. opening operation voltage | V | AC264/143 |
Max./min. Motor Voltage | V | AC242/187 |
Rated pressure of SF6 gas (psig) | MPa | "0" |