Customization: | Available |
---|---|
Electricity Type: | AC |
Number of Pole: | 3 |
Still deciding? Get samples of US$ 900/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Unit | VACYC | VACFC | ||
Rated voltage | kV | 12 | 7.2 | 12 | 7.2 |
Rated current | A | 400 | 25-160 | 25-315 | |
Rated breaking current | kA | 3.2 | 40 | ||
Rated making current | kA | 4 | - | ||
Limit breaking capacity | kA | 4.5 | 40(100peak value) | ||
4s rated short time withstand current | kA | 4 | - | ||
Peak withstand current | kA | 10 | - | ||
1s overload withstand current | kA | 6 | - | ||
Rated transfer current | kA | - | 3.15 | ||
1 min rated power frequency withstand voltage | kV | 42 | 32 | 42 | 32 |
Lightning impulse withstand voltage | kV | 75 | 60 | 75 | 60 |
Power frequency withstand voltage of control circuit | kV | 2 | 2 | ||
Rated operating voltage | V | 220V(AC/DC optional) | |||
Operating voltage range | V | 75%-100% Ue | |||
Maximum operating current | A | <7.5 | |||
Rated current of auxiliary contact | A | 5 | |||
Life electrical AC3 | Thousand times | 25 | |||
Life electrical AC4 | Thousand times | 10 | |||
Life mechanical | Thousand times | 50 | |||
Rated operating frequency | times/h | 300 | |||
Short time operating frequency | 20s | 600 | |||
Closing time | ms | ≤40 | |||
Opening time | ms | ≤35 | |||
Average closing speed | m/s | ≥0.4 | |||
Average opening speed | m/s | ≥0.45 | |||
Three phase non-simultaneity | ms | ≤5 | |||
Clearance between open contacts | ms | ≥5 | ≥3.5 | ≥5 | ≥3.5 |
Over travel | mm | ≥1.5 | |||
Main circuit resistance | μΩ | ≤150 | ≤150 Not including fuse |