Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 9/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
VACEM's impressive range of electrical products includes vacuum interrupters, embedded poles, and more. Their vacuum interrupters are made of ceramics and boast a voltage range of 1.14kV to 40.5kV, current from 63A to 4000A, and a rated short circuit breaking current from 2kA to 40kA. These products comply with both national and international standards, including GB and IEC standards.
VACEM has undergone three large-scale technical transformations and has introduced advanced production processing equipment from Germany and the United States. As a result, they now have first-class technology equipment and perfect testing means. Their products are characterized by standardization, seriation, miniaturization, and specialization.
VACEM also has an experienced R&D team, a complete and mature R&D program, and a special department dedicated to organizing the development of new products. To stay ahead of industry technology trends, VACEM has established long-term cooperative relationships with other well-known companies.
Specification of VI
Parameter item | Unit | Data |
Rated voltage | kV | 12 |
Rated current | A | 400 |
Rated frequency | Hz | 50/60 |
Rated short-time power frequency withstand voltage(1 min) | kV | 10 |
Rated lightning impulse withstand voltage | kV | 16 |
Rated short-circuit breaking current | kA | 8 |
Rated peak withstand current | kA | 20 |
Rated short-circuit making current | kA | 20 |
Rated short-time withstand current | kA | 8 |
Rated short-circuit duration | s | 1 |
Breaking operation of rated short circuit breaking current | times | 30 |
Electrical life | times | 10000 |
Mechanical life | times | 10000 |
Contact closing force due to bellows and atomsphere | N | 60±20 |
Force required to hold contact open at full stroke | N | 90±30 |
Circuit resistance at lowest rated contact force | μΩ | ≤35 |
Contact limit erosion | mm | 3 |
Internal gas pressure | Pa | ≤1.33×10-3 |
Weight of moving parts | kg | 0.3 |
Storage life | year | 20 |
Parameter item | Unit | Data |
Rated clearance between open contacts | mm | 4±0.5 |
Average opening speed | m/s | 1.1±0.2 |
Average closing speed | m/s | 0.6±0.2 |
Rated contact pressure | N | 600±100 |
Contact bouncing duration at closing operation | ms | ≤2 |
Closing and opening non-simultaneity of contacts | ms | ≤2 |
Maximum rebound during opening | mm | ≤2 |
Rated contact stroke | mm | 1.5±0.5 |