TEM | UNIT | DATA | |||||
Rated voltage | kV | 12 | |||||
Rated frequency | Hz | 5 0 |
|||||
Rated current | A | 630 | |||||
Rated power frequency 1min withstand voltage |
Disconnector | kV | 48 | ||||
Pole to pole/pole to earth | kV | 42 | |||||
Rated liahtning impulse withstand voltage(1.2/50μs) |
Disconnector | kV | 85 | ||||
Vacuum isolation | kV | 75 | |||||
Pole to pole/Pole to earth | kV | 75 | |||||
Rated short-circuit making current | kA | 50/63 | |||||
Rated short-time withstand current | kA/s | 20(4)/25(3) | |||||
Rated peak withstand current | kA | 50/63 | |||||
Rated short-circuit breaking current | kA | 20/25 | |||||
Short-time withstand current of Earthing-circuit | kA | 20(4) |
ITEM | UNIT | DATA | |
Rated voltage | kV | 12 | |
Rated frequency | Hz | 50 | |
Rated current | A | 630 | |
Rated power frequency 1min withstand voltage |
Disconnector | kV | 48 |
Pole to pole/pole to earth | kV | 42 | |
Rated lightning impulse withstand voltage(1.2/50us |
Disconnector | kV | 85 |
Vacuum isolation | kV | 75 | |
Pole to pole/Pole to earth | kV | 75 | |
Rated short-circuit making current | kA | 50/63 | |
Rated short-time withstand current | kA/s | 20(4)/25(3) | |
Rated peak withstand current | kA | 50/63 | |
Rated short-circuit breaking current | kA | 20/25 | |
Short-time withstand current of Earthing-circuit | kA | 20(4) |
Suppliers with verified business licenses