Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 9/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Are you looking for a reliable and high-performance vacuum interrupter for your medium voltage switchgear? Look no further than the 12kv VAC201 Vacuum Interrupter!
Crafted with precision and expertise, this vacuum interrupter boasts a ceramic insulating shell that ensures maximum durability and longevity. The middle sealing or built-in fixed shielding tube provides added protection and security, while the copper and chromium alloy contact material guarantees optimal conductivity and performance.
But that's not all - the 12kV series vacuum interrupter also features a streamlined and optimized structure that enhances its overall efficiency and effectiveness. Whether you're looking to upgrade your existing switchgear or invest in a new and improved solution, the 12kv VAC201 Vacuum Interrupter is the perfect choice for any medium voltage application.VI is mainly applied to VJCZ5-12 and VCKG-12 series MV vacuum contactors. Meets or exceeds the requirement of IEC62271-100 and E2 level in GB1984-2003.
Specification of VI
Parameter item | Unit | Data |
Rated voltage | kV | 12 |
Rated current | A | 630 |
Rated frequency | Hz | 50/60 |
Rated short-time power frequency withstand voltage(1 min) | kV | 42 |
Rated lightning impulse withstand voltage | kV | 75 |
Rated connecting current | kA | 6.3 |
Rated breaking current | kA | 5.04 |
Rated maximum sectional current | kA | 6.3 |
Rated minimum sectional current | A | 120 |
Rated short-time withstand current | kA | 6.3 |
Rated short-circuit duration | s | 4 |
Mechanical life | ten-thousand times | 30 |
Rated breaking time AC3 | ten-thousand times | 15 |
Rated breaking time AC4 | ten-thousand times | 6 |
Contact closing force due to bellows and atomsphere | N | 60±20 |
Force required to hold contact open at full stroke | N | 90±30 |
Circuit resistance at rated contact force | μΩ | ≤50 |
Contact limit erosion | mm | 3 |
Internal gas pressure | Pa | ≤1.33×10-3 |
Weight of moving parts | kg | 0.5 |
Storage life | year | 20 |
Parameter item | Unit | Data |
Rated clearance between open contacts | mm | 6±1 |
Average opening speed | m/s | 0.6±0.2 |
Average closing speed | m/s | 0.3±0.1 |
Rated contact pressure | N | 110±20 |
Contact bouncing duration at closing operation | ms | ≤3 |
Closing and opening non-simultaneity of contacts | ms | ≤1 |
Rated contact stroke | mm | 2±0.5 |