Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 9/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Get ready to experience the power of VACEM's top-of-the-line electrical products! Our main products include the highly sought-after vacuum interrupter and embedded pole, both of which are designed to meet the highest standards of quality and performance. Our vacuum interrupter is made of top-grade ceramics and boasts a voltage range of 1.14kV to 40.5kV, current from 63A to 4000A, and rated short circuit breaking current from 2kA to 40kA. VI is mainly applied to VCKG3/VJCZ5 and VCZG1-7.2 series MV AC vacuum contactor. Meets or exceeds the requirement of IEC62271-100 and E2 level in GB1984-2003.
At VACEM, we take pride in complying with relevant national and international standards, including GB and IEC standards. We've undergone three large-scale technical transformations and have introduced advanced production processing equipment from Germany and the United States. As a result, we have first-class technology equipment and perfect testing means, and our products are characterized by standardization, seriation, miniaturization, and specialization.
Our experienced R&D team and complete, mature R&D program ensure that we stay ahead of the curve when it comes to industry technology. We even have a special department dedicated to organizing the development of new products. To accurately grasp the development trend of industry technology, we establish long-term good relations of cooperation with other well-known companies.
Specification of VI
Parameter item | Unit | Data |
Rated voltage | kV | 7.2 |
Rated current | A | 250/630 |
Rated frequency | Hz | 50/60 |
Rated short-time power frequency withstand voltage(1 min) | kV | 32 |
Rated lightning impulse withstand voltage | kV | 60 |
Rated connecting current | kA | 6.3 |
Rated breaking current | kA | 5.04 |
Rated maximum sectional current | kA | 6.3 |
Rated minimum sectional current | A | 120 |
Rated short-time withstand current | kA | 6.3 |
Rated short-circuit duration | s | 4 |
Mechanical life | ten-thousand times | 30 |
Rated breaking time AC3 | ten-thousand times | 15 |
Rated breaking time AC4 | ten-thousand times | 6 |
Contact closing force due to bellows and atomsphere | N | 60±20 |
Force required to hold contact open at full stroke | N | 90±30 |
Circuit resistance at rated contact force | μΩ | ≤50 |
Contact limit erosion | mm | 0.4 |
Internal gas pressure | Pa | ≤1.33×10-3 |
Weight of moving parts | kg | 0.4 |
Storage life | year | 20 |
Parameter item | Unit | Data |
Rated clearance between open contacts | mm | 5±1 |
Average opening speed | m/s | 0.6±0.2 |
Average closing speed | m/s | 0.3±0.1 |
Rated contact pressure | N | 110±20 |
Contact bouncing duration at closing operation | ms | ≤2 |
Closing and opening non-simultaneity of contacts | ms | ≤2 |
Rated contact stroke | mm | 2±0.5 |