Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 1000/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12(G) series, the ultimate outdoor H.V. vacuum circuit breaker! This top-of-the-line switch equipment is designed for the English language's native speakers who crave excitement and spirited reading experiences. With a tri-phase AC 50Hz and a rated voltage of 12kV, this circuit breaker is ready to take on any challenge. Whether it's breaking, closing load current, overload current, or short-circuit current, this powerhouse is perfect for both urban and rural electrical power distribution systems.
But that's not all! The ZW32-12G circuit breaker also comes with a fantastic isolator combination electric appliance. Equipped with an isolation blade that boasts an evident fracture, this circuit breaker takes safety to a whole new level. You can trust that your electrical power distribution system is in good hands with this remarkable product.
So why wait? Upgrade to the 12kv Outdoor Medium Voltage Vacuum Circuit Breaker with Disconnector today! With its impressive features and keywords like Vacuum Circuit Breaker, Outdoor Vacuum Circuit Breaker, and Vcb on Pole, you know you're getting the best of the best. Don't miss out on this incredible opportunity to enhance your electrical power distribution system.
Item | Unit | ZW32-12(G)/400-12.5 | ZW32-12(G)/630-16 | ZW32-12(G)/630-20 | |
Rated voltage | kA | 12 | |||
Rated current | A | 400 | 630 | 630 | |
Rated short circuit breaking current | kA | 12.5 | 16 | 20 | |
Rated short circuit making current (peak) | kA | 31.5 | 40 | 50 | |
Rated peak withstand current | kA | 31.5 | 40 | 50 | |
Rated short time withstand current | kA | 12.5 | 16 | 20 | |
Rated short circuit duration | S | 4 | |||
Rated insulation level | 1min power frequency withstand voltage | kV | Phase to phase, to ground 42; fracture 48 | ||
lightning impulse withstand voltage (peak) | kV | Phase to phase, to ground 75;fracture 85 | |||
Rated sequence of operations | O-0.3s-C0-180s-CO | ||||
Rated short circuit current breaking time | time | 30 | |||
Mechanical life | time | 10000 | |||
Rated operation voltage (opening, closing coil) | V | DC220,110; AC220 | |||
Allowable attrition thickness of moving and fixed contact | mm | 3 | |||
Over-circuit release rated current | A | 5 | |||
Current transformer ratio | 200/5 400/5 600/5 | ||||
Clearance between open contacts | mm | 9±1 | |||
Contact over travel | mm | 2±0.5 | |||
Average opening speed | m/s | 1.2±0.3 | |||
Average closing speed | m/s | 0.6±0.2 | |||
Opening time | ms | 30~60 | |||
Closing time | ms | 20~40 | |||
Closing bounce time | ms | ≤2 | |||
Tri-phase opening and closing synchronous | ms | ≤2 | |||
Each phase loop DC resistance | μΩ | ≤80 | |||
Stored energy motor | Rated voltage | V | -220 | ||
Rated power | W | 200 | |||
Stored energy time | S | ≤8 | |||
Weight | Kg | 85, 125 (with G) |