Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 9/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Are you in need of a high-quality vacuum interrupter for your circuit breaker? Look no further than the 12kv High Voltage Vacuum Interrupter VAC307B! This top-of-the-line product is designed with the latest technology to ensure optimal performance and reliability. VI is mainly applied to VZN63-12kV series indoor MV vacuum circuit breaker. Meets or exceeds the requirement of IEC62271-100 and E2 level in GB1984-2003.
Crafted with a ceramic insulating shell and copper and chromium alloy contact material, this vacuum interrupter is built to last. It also features a middle sealing or built-in fixed shielding tube, which provides additional protection and enhances its overall durability.
Whether you're in the market for vacuum circuit breaker parts or simply need a reliable vacuum interrupter for your high voltage applications, the 12kv High Voltage Vacuum Interrupter VAC307B is a perfect choice. With its advanced design and superior construction, you can trust that this product will deliver exceptional performance and longevity.
Specification of VI
Parameter item | Unit | Data |
Rated voltage | kV | 12 |
Rated current | A | 2000 |
Rated frequency | Hz | 50/60 |
Rated short-time power frequency withstand voltage(1 min) | kV | 42 |
Rated lightning impulse withstand voltage | kV | 75 |
Rated short-circuit breaking current | kA | 31.5 |
Rated peak withstand current | kA | 80 |
Rated short-circuit making current | kA | 80 |
Rated short-time withstand current | kA | 31.5 |
Rated short-circuit duration | s | 4 |
Rated single capacitor bank breaking current | A | 630 |
Rated back to back capacitor bank breaking current | A | 400 |
Breaking operation of rated short circuit breaking current | times | 30 |
Mechanical life | times | 10000 |
Contact closing force due to bellows and atomsphere | N | 160±50 |
Force required to hold contact open at full stroke | N | 260±50 |
Circuit resistance at lowest rated contact force | μΩ | ≤20 |
Contact limit erosion | mm | 3 |
Internal gas pressure | Pa | ≤1.33×10-3 |
Weight of moving parts | kg | 1.6 |
Storage life | year | 20 |
Parameter item | Unit | Data |
Rated clearance between open contacts | mm | 11±1 |
Average opening speed | m/s | 1.1±0.2 |
Average closing speed | m/s | 0.6±0.2 |
Rated contact pressure | N | 3100±200 |
Contact bouncing duration at closing operation | ms | ≤2 |
Closing and opening non-simultaneity of contacts | ms | ≤2 |
Maximum rebound during opening | mm | ≤2 |
Rated contact stroke | mm | 3.5±0.5 |